Home > Blog > Top 10 Glashaus Systems in China: Wintergarten Aluminium, Gartenhaus and Terrassentüren Specs with FOB Pricing
Top 10 Glashaus Systems in China: Wintergarten Aluminium, Gartenhaus and Terrassentüren Specs with FOB Pricing
Aluminium Glashaus / Wintergarten with thermal break frame and double glazing, residential installation – ROGENILAN
Glashaus sourcing for the German-speaking market starts with four numbers, not with a photo: the Uw value the building authority will accept under GEG, the fRsi condensation margin under DIN 4108-2, the Schneelastzone your roof glazing has to carry under DIN EN 1991-1-3, and the Windlastzone for the mullion under DIN EN 1991-1-4. This page gives selection tables for each, plus 6063-T5/T6 mechanical data, PA66GF25 insulation strip widths, DIN 18008 overhead glazing rules, DIN EN 1627 RC ratings for Terrassentüren, FOB price bands and 40HQ loading math. All figures are from ROGENILAN shipped batches and are meant to replace verbal quotations.
1. Glashaus, Wintergarten, Gartenhaus: German terms and permit class
German buyers use six different words for what English catalogues collapse into “sunroom” or “greenhouse”. Quoting the wrong one produces an RFQ that cannot be permitted. The terms differ by heating status, which decides whether GEG energy rules apply at all.
Terminology table
German term
Literal meaning
Heated?
GEG applies?
Typical Uw target
Glashaus
Glass house
Either
If heated
1.3-1.9
Wintergarten (warm)
Heated conservatory
Yes
Yes
≤ 1.3
Wintergarten (kalt)
Unheated conservatory
No
No
Not regulated
Gartenhaus
Garden house / shed
Rarely
No
n/a
Gewächshaus Glas
Glass greenhouse
No
No
Single glazing OK
Terrassentür
Terrace door element
Adjacent to heated room
Yes
≤ 1.3
A Kaltwintergarten is treated as an unconditioned buffer space: no GEG U-value obligation, no heating load in the EnEV/GEG balance. A Warmwintergarten becomes conditioned floor area and the separating Terrassentür between house and conservatory must meet the GEG reference value of Uw 1.3 W/m²K. Specifying the separation door as a Kaltwintergarten element is the single most common permit rejection.
Which permit class applies
Baugenehmigung required – any heated Wintergarten, any structure with a fixed foundation above local volume limits, and all structures in the Außenbereich (outside the building envelope of a Bebauungsplan).
Verfahrensfrei (no permit) – most Gartenhaus and Gewächshaus up to the Bundesland volume threshold, provided they have no Feuerstätte, no sanitary room and no permanent habitation.
Genehmigungsfreistellung – a mid-tier procedure in several Bundesländer where the authority has one month to object; the file still needs Statik (structural calculation) and a Wärmeschutznachweis.
Volume is counted as Brutto-Rauminhalt (external envelope), not usable floor area.
Because the threshold differs by state, the RFQ should state the target Bundesland. A 32 m³ Gartenhaus is verfahrensfrei in Nordrhein-Westfalen (30 m³ limit applies to certain structures) but falls into a different class in Bayern, and roof overhangs count toward the envelope volume. General market background on these product families is covered in Sunrooms 4 Season Factory in China.
2. Wintergarten Aluminium: profile series and thermal break
Aluminium is the default structural material for Wintergarten in Germany because the roof bars have to carry snow load with a span of 1.2-2.4 m and a section depth small enough to keep sightlines. uPVC creeps under sustained load at summer bar temperatures above 70 °C, which is why uPVC is largely restricted to Gartenhaus wall panels.
Alloy and mechanical data
Alloy / temper
Tensile Rm (MPa)
Yield Rp0.2 (MPa)
Elongation (%)
Where used
6063-T5
160
110
8
Roof bars, wall mullions
6063-T6
205
170
10
Long-span roof beams
6060-T66
215
160
10
Slim Terrassentür frames
6061-T6
290
240
10
Corner posts, ridge beams
6082-T6
310
260
10
Heavy snow zone ridge
Wall thickness follows the load path: 1.4 mm minimum on non-structural cover profiles, 2.0 mm on mullions and transoms, 2.5-3.0 mm on ridge beams and on any profile that carries a roller track or a door hinge. For Snow Load Zone 3 with a 2.4 m bar span, the ridge beam is specified in 6082-T6 at 3.0 mm rather than 6063-T5.
Insulation strip width and resulting Uf
Series
Frame depth (mm)
Strip (PA66GF25)
Uf (W/m²K)
fRsi
Typical use
WG-60
60
14 mm
3.2
0.65
Kaltwintergarten
WG-75
75
20 mm
2.6
0.71
Gartenhaus, cool rooms
WG-90
90
24 mm
2.2
0.74
Standard warm Wintergarten
WG-110
110
34 mm
1.7
0.79
GEG-compliant heated
WG-130
130
44 mm
1.4
0.82
KfW / BEG subsidy projects
WG-150
150
54 mm
1.1
0.85
Passive-house class
PA66GF25 (polyamide 66 with 25 % glass fibre) is used rather than PVC because its coefficient of thermal expansion (2.5 × 10⁻⁵ K⁻¹) is close to aluminium (2.3 × 10⁻⁵ K⁻¹). PVC strips expand 3-4 times more, which opens a gap at the strip-to-chamber interface after a few heating seasons and degrades the Uf value measured on the finished frame.
3. GEG and DIN 4108: the numbers the authority checks
Two independent checks decide whether a Wintergarten passes: the declared Uw value against the GEG reference, and the fRsi surface temperature factor against DIN 4108-2. A project can pass the first and fail the second.
U-value limits by application
Element
GEG reference Uw
Practical ROGENILAN range
Comment
Heated Wintergarten wall
1.3
1.4-1.9
Needs WG-110 or better
Heated Wintergarten roof
1.4
1.1-1.6
Roof glazing Ug dominates
Separating Terrassentür
1.3
1.2-1.5
Door to the house, always heated side
Kaltwintergarten
Not regulated
2.6-3.2
WG-60 / WG-75 acceptable
Gartenhaus
Not regulated
3.2-5.9
Non-thermal-break allowed
GEG Anlage 3 sets the 1.3 W/m²K reference for replacement windows and doors in heated envelopes. The Uw value has to be declared with the calculation method stated (DIN EN ISO 10077-2 for frames, DIN EN 673 for the glazing centre-of-pane Ug), not as a single unverified number.
fRsi condensation criterion, limit 0.70
Construction
Uf (W/m²K)
fRsi at -5 °C / 20 °C / 50 % RH
DIN 4108-2 verdict
Aluminium, no break
5.9
0.52
Fail – mould risk
14 mm PA66GF25
3.2
0.65
Fail – marginal
20 mm PA66GF25
2.6
0.71
Pass
24 mm PA66GF25
2.2
0.74
Pass
34 mm PA66GF25
1.7
0.79
Pass
44 mm PA66GF25
1.4
0.82
Pass
54 mm PA66GF25
1.1
0.85
Pass
Budget note. The step from 14 mm to 20 mm strip costs roughly 6-9 USD/m² of frame but moves fRsi from 0.65 to 0.71. On a 22 m² Wintergarten with 34 m of frame perimeter this is about 240 USD of added cost against a condensation remediation that typically starts at 2,000 EUR. Ordering at the 0.65 point to save 240 USD is the trade-off that produces callbacks.
The criterion is evaluated at the coldest internal surface point, normally the glass edge or the frame-to-glazing junction, not at the frame centre. Warm-edge spacer bars (stainless steel or plastic, λ ≤ 0.5 W/mK) raise the glass-edge fRsi by 0.03-0.05 compared with an aluminium spacer and are specified as standard on WG-110 and above.
4. Schneelast and Windlast zones (DIN EN 1991)
Germany is divided into snow load zones 1-3 and wind load zones 1-4. The zone is set by the building location and drives bar spacing, bar depth and glass thickness. A Wintergarten specified for Zone 1 and shipped to a Zone 3 site in the Alpenvorland will not pass the Statik check.
Snow load zones to roof configuration
Zone
sk ground (kN/m²)
Ridge beam
Max bar span
Roof pitch
1
0.65
6063-T6, 2.5 mm
2.4 m
10-25°
2
0.85
6063-T6, 2.5 mm
2.1 m
10-25°
3
1.10
6082-T6, 3.0 mm
1.8 m
12-30°
3 + altitude > 800 m
1.35-1.60
6082-T6, 3.0 mm + steel insert
1.5 m
15-35°
Roof pitch below 10° is avoided because water and snow do not drain and the standing water load adds 0.10 kN/m² per 10 mm of ponding. Pitch above 30° increases the glass area and the summer solar gain without improving the structural case.
Wind zones to mullion deflection
Wind zone
q ref (kN/m²)
Mullion series
Deflection limit
Max mullion height
1 – inland
0.32
WG-75
L/200
2.6 m
2 – most of DE
0.39
WG-90
L/200
2.8 m
3 – north / coast
0.47
WG-110
L/250
3.0 m
4 – North Sea coast
0.56
WG-130 + steel insert
L/250
3.2 m
Deflection is checked under quasi-permanent combination at L/200 for inland sites and L/250 for coastal sites where the wind is combined with driving rain. Steel inserts are hollow galvanised sections pushed into the mullion chamber; they raise the moment of inertia by 2.5-3.5 times for about 4-7 USD/m of mullion. For the full frame classification behind these numbers see 门窗 Wholesaler in Foshan Guangdong.
5. Glazing: DIN 18008, Ug and g-value
German glass design follows DIN 18008-1 (general) and DIN 18008-2 (line-supported, overhead). The binding rule for a Wintergarten is that all overhead glazing must be laminated safety glass (VSG) with a verified residual load-bearing capacity, because a monolithic pane over a seating area has no post-breakage capacity.
Glass build-ups and measured data
Build-up
Type
Ug (W/m²K)
g-value
LT
Weight (kg/m²)
4-16Ar-4 low-e
Double
1.1
0.62
0.71
20
4-16Ar-4 solar control
Double
1.0
0.35
0.62
20
6-16Ar-6 low-e
Double
1.1
0.60
0.70
30
4-12Ar-4-12Ar-4
Triple
0.7
0.52
0.63
30
6-16Ar-6-16Ar-6
Triple
0.6
0.50
0.61
45
VSG 2×5 TVG -16Ar- 8.8
Roof, laminated
1.0
0.42
0.58
41
The g-value is the German solar energy transmittance (g-Wert) and is the number that decides summer overheating. For a south-facing Wintergarten without external shading, g above 0.50 pushes the internal temperature 12-18 K above ambient on a 30 °C day.
Overhead glazing rules
All panes above head height in a traffic area must be VSG with a residual capacity verified to DIN 18008-2.
Roof build-up is specified as 2 × 5 mm TVG laminated outer / 16 mm argon / 8.8 mm laminated inner, giving Ug 1.0 at 41 kg/m².
Walk-on or maintenance-access areas use 3-ply VSG; the middle ply carries the load after one outer ply breaks.
Edge cover into the frame must be at least 15 mm, and the glazing support must be continuous – point supports are not used in roof bars.
Argon fill is declared to DIN EN 1279-3 with a leakage rate below 1 % per year; the declaration is part of the CE file.
Summer thermal protection is documented under DIN 4108-2 and is separate from the winter U-value check. External roller shutters or an external awning are the only measures that remove the gain before it enters the glass; internal blinds reduce glare but leave 40-55 % of the energy in the room. Related glazing data for vertical elements is in Sliding Glass Doors Factory in China.
6. Terrassentüren: threshold, RC rating and barrier-free access
The Terrassentür is the element between the house and the Wintergarten, and it is the one that carries the GEG obligation, the security rating and the barrier-free requirement at the same time. These three pull in different directions: a low threshold for accessibility reduces the water-tightness class.
Threshold height and water tightness
Threshold
Height (mm)
DIN EN 14351-1 class
Barrier-free?
Use
Standard rebated
48
9A / E900
No
Exposed facades, wind zone 3-4
Medium
25
7A / E600
No
Standard terrace, sheltered
Low / barrier-free
20
5B / E450
Yes (DIN 18040-2)
Ground floor, accessible
Flush / drainage rail
5
4B / E300
Yes
Internal separation only
A 5 mm flush threshold is only acceptable where the door is protected by a roof overhang of at least one third of the door height and a drained channel in front of it. Specifying a flush threshold on an exposed north-west facade is the most common source of water ingress claims.
RC burglary resistance and hardware
Class (DIN EN 1627)
Resistance time
Glass
Hardware
Added cost (EUR/m²)
RC1 N
Basic
Float, 2-ply
Standard espagnolette
0
RC2
3 min, hand tools
VSG 8.8 mm
4-point locking, mushroom cams
38-55
RC2 N (glazing only)
–
VSG 8.8 mm
Standard locking
22-30
RC3
5 min, lever tools
VSG 10.8 mm
6-point, security strike plates
65-95
RC2 is the default in German residential specification and is what most insurers reference. RC2 N denotes glazing-only resistance and does not include the locking hardware, a distinction that is frequently missed in quotations. Locking points are spaced at 700-900 mm along the sash; a 2.4 m high Terrassentür needs at least four. Full door-side hardware data is in Sliding Patio Door Export from China.
7. Gartenhaus: the 30 m³ rule and kit configurations
Gartenhaus orders are driven by the permit-free volume threshold rather than by thermal performance. The buyer is optimising for the largest structure that still avoids a Bauantrag.
Volume thresholds by Bundesland
Bundesland
Verfahrensfrei up to
Notes
Nordrhein-Westfalen
30 m³
No Feuerstätte, no Aufenthaltsraum
Bayern
75 m³
Higher threshold, but Bebauungsplan can override
Baden-Württemberg
40 m³
Roof overhang counts toward volume
Niedersachsen
40 m³
Boundary setback 3 m applies
Hessen
30 m³
Außenbereich excluded entirely
The volume is the external envelope, so a 4.0 × 3.0 m footprint with a 2.5 m wall and a 0.5 m pitched roof rise is 4.0 × 3.0 × 3.0 = 36 m³ with the roof, above the 30 m³ line in NRW and Hessen and below it in Bayern. Buyers routinely order 4 × 3 m and then discover the permit question, which is why the kit should be offered in 3.5 × 2.5 m (26 m³) and 4.0 × 3.0 m (36 m³) variants.
Kit configurations
Kit
Footprint
Volume
Series
Wall panel
FOB (USD/kit)
GH-S
2.5 × 2.5 m
19 m³
WG-60
28 mm sandwich
780-1,150
GH-M
3.5 × 2.5 m
26 m³
WG-75
28 mm sandwich
1,180-1,720
GH-L
4.0 × 3.0 m
36 m³
WG-75
40 mm sandwich
1,760-2,480
GH-XL
5.0 × 3.5 m
61 m³
WG-90
40 mm sandwich
2,760-3,940
Sandwich panels are 0.4 mm aluminium skins on a PE or PU core. A 28 mm panel gives U 0.85 W/m²K, a 40 mm PU panel gives U 0.55 W/m²K. Panels are used for walls only; the roof stays glazed or uses 16 mm polycarbonate multiwall on the GH-S.
8. Gewächshaus Glas: the unheated branch
Gewächshaus Glas orders have no thermal regulation to satisfy and are bought on light transmission, hail resistance and price. This is a different specification exercise from a Wintergarten and the two should not share a quotation sheet.
Glass versus polycarbonate
Property
Horticultural glass 4 mm
Twinwall PC 10 mm
Twinwall PC 16 mm
VSG 8.8 mm
Light transmission
0.90
0.78
0.74
0.86
U-value (W/m²K)
5.8
3.0
2.4
5.6
Weight (kg/m²)
10
1.7
2.5
17
Hail resistance
Low
High
High
Medium
Service life (years)
15-20
10-12
12-15
20-25
FOB (USD/m²)
9-14
12-18
17-24
34-46
Polycarbonate loses 8-12 % of light transmission in the first five years through UV yellowing unless a co-extruded UV layer is specified. Glass gains no such penalty and is preferred where the buyer is growing rather than storing.
Ventilation and thermal mass
Roof vent area should equal 15-20 % of floor area; below 12 % the internal temperature exceeds 40 °C in German summer.
Side vents on opposite walls create cross ventilation; a single-sided vent does not.
Automatic vent openers are wax-cylinder type, set to start at 18-22 °C, and need no power.
A 100 mm concrete or stone floor adds thermal mass and cuts the night-time temperature swing by 6-9 K.
Water barrels along the north wall are the low-cost version of the same effect, worth 3-4 K of swing reduction.
Projects that combine a growing area with a seating area are better served by a Kaltwintergarten with a glazed partition than by a Gewächshaus, because the seating side needs the DIN 18008 overhead laminated rule that horticultural glazing does not meet. See Garden Room Wholesaler in China.
9. FOB price bands and landed cost
Prices below are FOB Shenzhen or Guangzhou, in USD per square metre of glazed envelope, for a complete kit: profiles, glazing, gaskets, hardware, fixings and shop drawings. They exclude installation, local transport and German VAT.
FOB bands by series and volume tiers
Series
20-99 m²
100-299 m²
300-799 m²
800+ m²
WG-60 (kalt)
88-118
83-112
78-105
73-98
WG-75
120-165
114-156
107-147
100-137
WG-90
155-215
147-204
138-192
129-179
WG-110
210-300
199-285
187-267
174-249
WG-130
265-385
252-366
236-343
220-320
Volume tiers are cumulative per contract year, not per order. Moving from the first to the fourth tier is a 17-21 % reduction and is available to a single buyer who consolidates a Wintergarten, a Gartenhaus and the house window package into one contract.
Landed cost: 22 m² Wintergarten to Hamburg
Line
Basis
Amount (EUR)
FOB kit, WG-110
22 m² at 268 EUR/m²
5,896
Sea freight + THC
6.4 m³, LCL
640
Insurance
0.35 % of CIF
24
Import duty
CN code 7610 10 90, 0 % MFN
0
Import VAT
19 % on CIF + duty
1,246
Customs clearance
Per entry
95
Inland to site
Hamburg region
380
Landed, excl. installation
8,281
Per m²
376
Budget note. Import VAT is recoverable by a registered German business and should not be treated as a cost in a commercial comparison. Excluding it, the landed figure is 7,035 EUR or 320 EUR/m². The 7610 series covers aluminium structural units and glazed panels; the exact code depends on whether the kit ships as panels or as cut profiles, which is worth confirming with the Spediteur before quoting.
Wintergarten and Gartenhaus kits ship as flat-packed profile bundles plus glass crates. Glass is the constraint: it is heavy, it is breakable and it cannot be de-nested.
Commercial terms
Item
Term
MOQ
20 m² glazed envelope (Wintergarten) / 5 kits (Gartenhaus)
Lead time
30-45 days after approved shop drawings
Drawing time
7-10 days, included in lead time
Payment
30 % deposit, 70 % against B/L copy; LC at sight accepted
Sample
1.2 m corner section with glazing, 180-260 USD, credited on first order
Packing
Profiles in PE foam + kraft; glass in A-frame steel crates, ISPM-15
Warranty
10 years on profiles and coating, 5 years on sealed units
40HQ loading math
Item
Per unit
40HQ capacity
Profile bundle
1.4 m³ per 22 m² kit
18-20 kits by volume
Glass crate
0.9 m³, 1,050 kg
24 crates by weight (25 t limit)
Hardware cartons
0.12 m³
Included in bundle space
Practical mixed load
22 m² kit
16-18 kits
Gartenhaus GH-M kit
1.9 m³
26-30 kits
A 40HQ payload limit of 25-26 t is reached before the 68 m³ volume limit when glass is included. Splitting a large order so that profiles travel in one container and glass in a second is usually cheaper than consolidating, because the profile-only container reaches volume limit at roughly 12 t.
11. Installation sequence and three failure points
German installation practice separates the structural anchoring, the water management layer and the air-sealing layer. Doing these in one step is what produces the callbacks.
Eight-step sequence
Set the base: levelled concrete strip or steel plinth, +/- 2 mm over the full perimeter, with a capillary break.
Anchor the sill track with M10 stainless anchors at 400 mm centres, not into insulation without load-distributing spacers.
Erect corner posts and plumb them before any glazing is lifted – a 3 mm lean at this stage becomes 12 mm at the ridge.
Fit the ridge beam and check the bar span against the shop drawing before glazing.
Install the roof glazing from the ridge downward, with the laminated pane seated on continuous setting blocks.
Apply the EPDM or butyl sealing tape at the bar-to-glass junction, then the pressure plate and cover cap.
Install wall glazing and Terrassentüren, adjust the rollers before the gaskets are compressed.
Commission: check drainage channels with 5 litres of water per metre, check vent openers, check locking points.
Three failure points
Sealing tape applied under tension. EPDM shrinks 1-2 % in the first winter. Laid straight it pulls away at the corner; the tape is laid with a 3 % surplus and compressed, never stretched.
Drainage channel blocked by sealant. Roof bar channels must stay open. Applying silicone across the channel mouth during glazing blocks the weep path and the first heavy rain backs up into the frame.
Base not isolated from the house slab. A Wintergarten base cast against the house slab without a thermal separation transmits heat and creates a cold bridge at the junction, which shows as condensation on the internal face in January.
Installation labour for a 22 m² Wintergarten in Germany runs 2,800-4,500 EUR for a two-person crew over 4-6 days, excluding the electrician for vent openers and shading. Frame-side installation data for adjacent products is in Casement Windows Factory in China.
12. Case study: 34 houses, Munich region
A developer building 34 terraced houses in the Munich Land district ordered WG-110 Wintergarten units averaging 18.6 m² plus a separating Terrassentür per house between 2024 and 2025.
Capital cost comparison
Line
Local German supplier
ROGENILAN, landed
Delta
Kit, 18.6 m²
9,180 EUR
5,410 EUR
-41.1 %
Terrassentür RC2
2,640 EUR
1,580 EUR
-40.2 %
Roof glazing upgrade
1,320 EUR
780 EUR
-40.9 %
Installation
3,450 EUR
3,450 EUR
0 %
Per house
16,590 EUR
11,220 EUR
-32.4 %
34 houses
564,060 EUR
381,480 EUR
-182,580 EUR
Twelve-month defect record
Metric
Local supplier (previous phase)
ROGENILAN phase
Condensation complaints
11 of 34 houses
1 of 34 houses
Water ingress at threshold
4 of 34
1 of 34
Adjustment callouts (per house)
1.6
0.9
Glass breakage in transit
0.4 % of panels
0.7 % of panels
Sealed unit fogging, 12 months
0.2 %
0.3 %
The condensation difference is explained by the strip width: the previous phase used a 20 mm PA66GF25 strip (fRsi 0.71, at the limit), the ROGENILAN phase used 34 mm (fRsi 0.79). Transit breakage was marginally higher on the shipped phase and was absorbed under the crate-level replacement clause rather than disputed.
13. Aluminium versus uPVC versus timber
Material choice for a Glashaus is a structural question before it is a thermal one. The comparison below is for a heated Wintergarten in Snow Zone 2.
Nine-point comparison
Property
Aluminium thermal break
uPVC
Timber-aluminium
Bar span at Zone 2
2.1 m
1.4 m
1.8 m
Uf achievable
1.1-3.2
1.0-1.4
0.9-1.3
Creep at 70 °C bar
None
1.5-3 mm/m
None
Coating life
25-40 y (Qualicoat)
n/a
8-12 y (paint)
Maintenance interval
Clean only
Clean only
Re-coat 6-8 y
Section sightline
45-60 mm
70-95 mm
80-110 mm
Recycled content
60-75 %
Low
Low
FOB (USD/m²)
88-385
70-190
210-520
Fire behaviour
A1
B1, melts
B2
Selection by scenario
Heated Wintergarten, Snow Zone 2-3: aluminium WG-110 or WG-130. uPVC cannot take the bar span.
Kaltwintergarten: aluminium WG-60 or WG-75. No thermal obligation, minimise cost.
Gartenhaus under 30 m³: aluminium WG-60 with sandwich panels; uPVC acceptable for wall panels.
Denkmalschutz (listed building): timber-aluminium, external aluminium face with internal timber.
Gewächshaus: aluminium with horticultural glass or polycarbonate, no thermal break needed.
A Glashaus RFQ that omits the zone data will be answered with a placeholder price. The following two lists are what a factory needs to quote without assumptions.
Technical – 8 items
Footprint and ridge height, plus roof pitch.
Bundesland and postcode, to fix Schneelastzone and Windlastzone.
Terrassentür: number of leaves, threshold height, RC class, opening direction.
Shading: external awning, roller shutter or internal blind, and the fixing provision required.
Surface finish: RAL, Qualicoat class, and whether Qualimarine is needed (coastal, within 5 km of sea).
Commercial – 8 items
Total glazed area and number of identical units.
Incoterm and port (FOB Shenzhen / FOB Guangzhou / CIF Hamburg / CIF Rotterdam).
Delivery schedule and whether the site can take a full container.
Payment terms and whether LC at sight is required.
Required certificates: CE to DIN EN 14351-1, DIN EN 1090-1 for the load-bearing structure.
Declaration documents: Leistungserklärung, U-value calculation, DIN 18008 glass calculation.
Spare parts allowance: gasket, setting blocks, 2 % extra glazing.
Warranty period and the claim procedure, including who pays for a re-glaze.
Note on DIN EN 1090-1. A Wintergarten with a load-bearing aluminium structure is a construction product under the BauPVO and needs a CE mark with an execution class (EXC 1 or EXC 2). The factory must hold a certified factory production control system to issue it. Ask for the certificate number before ordering, not after.